MENU

TA Series – Timed Abort Station

General Description

The TA-123 is a countdown timer that includes a red mushroom abort button. The TA-123 is designed show amount of time remaining prior to a fire suppression system discharge The timer can be set for up to 99:59 and can accommodate various insurance requirements. It is designed to mount on a 3 gang switch box and may be embedded in a Graphic annunciator

Specifications

  • Dimensions: 37.7″ L x 2.9″ D x 3.80″ H (95.76 cm x 7.37 cm x 9.6 cm)
  • Weight: 4.7 lbs (2.13 kg.)
  • Input: 24 vdc, Filtered & Regulated
  • Standby: 155ma
  • Activated: 175ma
  • Display Size: 36″ L x 2.1″ H (91.4 cm x 5.3 cm)
  • Display Resolution: 120 x 7 pixels

Features

Easily programmed to

1. Reset to original time when ABORT is depressed.
2. Reset to original time when ABORT is depressed unless time left is less than 10 seconds, in which case resets to 10 seconds (jumper option)
3. Halt (stop time) when ABORT is depressed.
4. Count down to 10 seconds and hold when ABORT is depressed.

Operation

The digital countdown timer is activated by contact closure and requires 24VDC power (filtered and regulated power recommended but not required).

Panel operated ABORT contact may be connected to either reset or halt time.

The digital countdown timer uses its own internal clock and must be programmed to coincide with the time delay on the control panel that powers it. Its use is for the reference of the time remaining between the start and finish of the suppression system control unit time delay period. It is not an integral part of the suppression system control unit and does not affect the control unit time delay settings. Load terminals may not be parallel linked. Each load is only capable of triggering its own, independent load.

Time Setting Switches

Switches S1 – S4 are used to set the initial count down time of the TA-123. Each is set to the digit of the initial count in the format of MM:SS. You can set minutes on S1 and S2 from 0 to 99 minutes. S3 and S4 are used to set the seconds from 0 to 59 seconds.

Please note that if S1 and S2 are set to 00 minutes then S3 and S4 may be set from 0 to 99 seconds.

Optional Jumpers & Wiring

J2 – Sonalert Enable. When enabled, the sonalert beeps once each second while the TA-123 is counting down. When the count reaches 00:00 the sonalert changes from a beep to a solid tone until the trigger signal is removed.

J3 – Changes the RESET and HALT to respond to some 3rd part requirements. When J3 is not enabled, RESET will stop the count, and when released, reset to the S1-S4 initial count time. When enabled, RESET will respond the same UNLESS the count is at 10 seconds or less. When the count is 10 seconds or less, RESET will cause the count to stop and resume at 10 seconds when released. When J3 is enabled, HALT will count down UNTIL the count reaches 10 seconds at which point it will hold. After HALT is released, the count will resume as normal from 10 seconds.

Wiring Diagram